THE COLLIERY GUARDIAN AND JOURNAL OF THE COAL AND IRON TRADES. Vol. CXV. FRIDAY, APRIL 12, 1918. No. 2989. Notes on the Maintenance of Turbo Alternators. By L. FOKES. The introduction of steam turbo plant for the generation of electrical power brought about a revolution in the design of electrical generators. Owing to the high speeds at which the plant had to operate, centrifugal forces hitherto unknown in connection with electrical machinery, ‘ together with other limitations which had to be provided for, entirely altered the design of the old slow speed alternators. In those machines driven by reciprocating engines, no serious difficulties due to centrifugal forces were encountered, as large generators were designed to run at low speeds, so that suitable adjustments could always be made to meet each case. However, in connection with turbo plant, the speed must neces- sarily be high, whether the plant be small or one of many thousands of kilowatts capacity. The frequency of the supply was readily obtained in slow speed sets by adjusting the number of poles in the rotor to suit the speed decided upon; but the scope in this direction is very limited with turbo alternators, because the diameter of the machine is bound to be reduced to a minimum, owing to the centrifugal forces. Hence turbo alternators do not have more than four poles, and in many cases only two. The frequency per second of the supply from an alternating current generator depends on the speed and the number of poles provided on the rotor. Given the number of pairs of poles and the revo- lutions per minute of a machine, the frequency of the supply is furnished by the formula _ N x R.P.M. -------- where N = number of pairs of poles on the rotor, and R.P.M. — revolutions per minute. For instance, a generator running at only 100 revolutions per minute in order to provide a frequency of 50 cycles must have — 30 pairs of poles, or sixty pole pieces. As already stated, turbo generators do not exceed four poles on the rotor, and to obtain a supply of i t i j -n u 50 X 60 50 cycles with such a machine the speed will be-------— = 1,500 revolutions per minute. If the rotor has only two poles, the speed will be 50 * — 3;000 revolutions per minute. In both these examples it should be noted that the reference is to pairs of poles, i.e., two pairs in the case of the four pole machine and one pair in that of the two pole generator. One of the chief difficulties with which the designer of high speed alternators is faced lies in this limita- tion to the possible diameter of the machine, so that as the capacity increases, instead of being able to make a machine of larger diameter, the extra capacity has to be obtained by making the generator longer. This does not present much difficulty from the mechanical standpoint, but the provision of the necessary ventilation for carrying off the heat developed, calls for considerable skill and ingenuity. In the case of slow speed generators, the heat was readily dissipated by the large surfaces presented for radiation, but owing to the large amount of heat developed in a comparatively small space, turbo generators require special consideration, and much attention has been devoted to the problem. An idea of the difficulty will be formed by con- . sidering the amount of heat to be dissipated in large turbo alternators. Take, as an instance, a generator of 10,000 k.v.a. capacity with an efficiency of 96 per cent. The heat generated in the machine and which has to be got rid of is equal to 400 kw., and when it is remembered that 1 kw. will raise 100 cu. ft. *of air 18 degs. Cent, in 1 min., such a machine would raise the temperature of 400 x 100 = 40,000 cu. ft. of air per minute to that extent. To force these large quantities of air through such a limited space, calls for very high velocities, as the airways are long and narrow, and velocities up to 5,000 ft. and 6,000 ft. per minute are used, or even more in some exceptional cases. The chief difficulty consists in getting the air to the hottest parts of the machine, which are in many cases so confined that very little air reaches them unless considerable pressure is used. There are at present two methods of supplying the air for cooling high-speed alternators. The first consists of suitable fans or air scoops attached to the rotor ends. This method is widely used for moderately sized machines, although the efficiency of the fans is very low, and considerable power is wasted, owing to the churning of the air when running at very high speeds. In very large sets, separate ventilation is often adopted, and this appears to have much to recommend it, and to be more efficient. Besides, the amount of air delivered to and forced through the generator can be adjusted to suit the load, and more economical working of the ventilation results. Provided the temperature of the air at the outlet does not differ greatly from that at the inlet, no benefit will result from increasing the quantity of air, as the power required to produce the ventilation lowers the over-all efficiency of the plant, so that it should be kept as low as possible consistent with ample ventilation. Systems of Ventilation. To appreciate thoroughly the necessity and also the difficulties in the proper maintenance of turbo alternators it is essential that the general construc- tion should be understood, and more especially is this desirable in connection with the ventilation, as when cleaning operations are undertaken, a know- ledge of the principles of ventilating a generator is of assistance in getting the work properly carried out, and the air ducts, etc., kept in proper order. There are several methods of conducting the heat from the machine, but only three of the better known and widely used systems will be referred to, i.e., the radial system, circumferential, and axial. Radial System. The Radial system of ventilation provides for the air being drawn in at each end of the rotor and discharged radially through the stator air ducts to the surrounding atmosphere or into a conduit for carrying the heated air to the outside of the building. As the heating of the rotor is only a small per- centage of that of the stator, its ventilation does not require the same consideration, and therefore Fig. 1. Fig. 2. Fig. 3. Stqtor Winding S tator Windir in one form of radial ventilation, shown in fig. 1, air is admitted to the air gap and forced out through the stator core. Owing to the restricted path for the air, the gap requires to be somewhat larger than otherwise necessary, so that a modification of fig. 1 is shown in fig. 2. It will be noticed that in addition to the air being received through the air gap, provision is made for passing some of it through ducts in the rotor running from end to end, and provided with outlets at right angles, to enable the air to pass across the air gap and out through the stator air ducts. This provides cooling air for the rotor and also allows of the air gap being reduced to a minimum for electrical purposes without having to allow the question of ventilation to influence its size. In these two figures, and the succeeding ones, the winged arrows indicate the inlet air, and those without wings represent the direction of the air leaving the machine. Circumferential Method. This is applied by admitting the air supply at one or more points in the outer casing of the stator, carrying it round a certain distance through the air ducts, and discharging it again through another opening in the casing. Sometimes four openings are provided, i.e., one at each quarter of the machine, in which case air may be admitted at each side and discharged top and bottom. However, two openings are usually sufficient. A section of such a machine is shown in fig. 3, the air inlet being indicated at the bottom, while the outlet appears at the top. The objection put forward to this method lies in the long and restricted path through which the air has to travel. Axial Flow. The methods just explained have one common disadvantage, i.e., that the heat generated in the core of the machine has to be conducted across the laminations to the air ducts. It is hardly necessary to explain that in all alternat- ing current machinery, the magnetic circuit is made up of thin sheets of iron or soft steel separated by sheets of prepared paper, the whole being held together in a solid mass by suitable bolts and clamps. The bolts are insulated from the core, so that contact cannot occur along the edges of the plates to connect them all together through the bolts. This construc- tion is necessary in order to reduce the eddy currents set up in the iron by the rapidly varying magnetic flux, which quickly causes the iron core to attain a very high temperature unless some provision is made to reduce these eddy-current Josses. Referring to fig. 4, a section of core is represented showing two radial air ducts. Taking a point B and striking a line upwards, it will be noticed that, in order for heat to get from the centre of the core above point B to either radial air duct, the heat must cross through numerous layers of paper and iron, from B to C, or from B to A. Paper being a poor heat conductor, renders the conduction path in that direction very poor, so that much local heating is liable to take place inside the core, and may possibly destroy the paper insulating sheets between the plates and be the means of raising the temperature of the core still higher. This heating may go still further and cause damage to the windings themselves, as the maximum heating of the stator iron of an alternator occurs just behind the teeth, or just at the back of the tubes carrying the windings. Referring to fig. 4, it will be seen that the sheets of iron or steel run from A to D, and that heat generated at A would be more readily conducted to D than it would be to C, even though the distance is shorter in the latter case. Hence if the ducts are so arranged that the air current passes across the plates instead of parallel with them, the heat can be carried off much more rapidly. It is found that heat conduction in the direction of the core plates is often more than ten times greater than it is from plate to plate through the paper insulation. This fact accounts for the introduction of the axial flow system, shown in fig. 5. The air enters at various points at right angles to the upright machine and after passing through the air ducts, enters a main duct in the centre of the machine, through which it is discharged. Dust Problems. From the figs, referred to, it is easy to appreciate the difficulty of removing dust from the various air ducts when once they are allowed to become blocked through infrequent cleaning and lack of attention to the condition of the air supply to the generator. Open Type Generators. These machines are fast being replaced or end covers added. Open type machines are objectionable in three ways, i.e., (1) they become very dirty; (2) the noise is excessive; (3) the heated air leaving the generator is objectionable. (1) When the air ducts of a machine become dirty, the ventilation is restricted, and if the machine has no margin of temperature rise before reaching a dangerous point, trouble is likely to occur. The dust usually encountered in collieries, though readily held in suspension in the surrounding air, very soon becomes caked and difficult to move once it settles down. This is specially so where the atmosphere is humid and oil vapour rises from the bearings. This dust often defies all the efforts of hand blowers and the like, and even compressed air fails to unstop the ducts once they are allowed to become blocked. The question of cleaning, however, will be dealt with later, but it is urged that all existing open type generators should be enclosed without delay, and suitable fans fitted to the rotor for increasing the ventilation. (2) The noise is very objectionable, especially when switchboard attendants have to remain within a short distance of the machines, as the constant noise drowns everything else, and no opportunity exists of hearing